Damped AC (DAC) technology

Damped AC (DAC) technology

Advanced DAC technology utilizes since 1999 voltage testing in combination with non-destructive diagnostic methods, such as partial discharge (PD) detection and dissipation factor (tan δ) measurement of the cable system and associated accessories.

On-site testing and diagnosis of Damped AC (DAC) of power cables is

  • a good alternative to traditional VLF and ACRT methods and less destructive,
  • attractive from the point of view of costs, logistics and execution efforts e.g. time, transportation, installation,
  • providing more complete information (PD localization and dielectric losses) about cable system condition,
  • fulfilling testing parameters as requested by the IEC 60060-3, IEEE 400, IEEE 400.4, IEC 60060-3, IEC 60480, IEC 62067, IEC 60270, IEC 63026 and IEEE 400.3.
  • implemented in testing recommendations of a number regional and national bodies e.g. PTPiREE, SEP, CENELEC, UK Power Networks, UNE and ACP OCRP-2024.
  • since more than 25 years used for distribution and transmission of on-shore and since more that 5 years in off-shore applications in many parts of the world.

To obtain the overall technical condition of a newly installed on- and offshore power cable systems and/or to evaluate the electrical, thermal and mechanical service aging the following diagnostic test will be performed and the results evaluated in relation to international guidelines:

  • High voltage damped AC (DAC) over-voltage testing
  • Partial discharge measurement and localization
  • Dielectric losses by the dissipation factor (tan δ) estimation

Damped AC (DAC) technology (IEEE 400, IEEE 400.4) has the advantage of non-destructive testing and the method provides deterministic values of partial discharge (PD) activities in the cable system as well as the dissipation factor (tan δ) of the overall cable system.

Long-Length Cable Circuits are more and more used for such renewable energy production e.g. on- and off-shore wind farms where the power cables used in those systems might have lengths up to 100 km.

PD-monitored DAC testing is an excellent and actually the only one method for non-destructive and effective way of such long lengths power cable circuits.

Due to its low input power demand the damped AC technology using Dual Power solution) and Dual Side PD detection makes it possible to energize very long lengths (up to 100 km) of AC and DC power cable with a high capacitance and to detect PD activities in complete cable systems.

It is applicable for

  • all types MVAC, HVAC and HVDC HV and EHV power cables.
  • on-site after-laying / commissioning, maintenance and diagnostic tests.
  • on-shore and off-shore

DAC is an approved testing methodology, in accordance with on-site testing test parameters from relevant international standards and recommendations (IEEE, IEC, CIGRE).

Conformity of damped AC (DAC) voltage testingto international standards, guidelines, recommendations and best practice

Since 25 years for testing and diagnosis of all types of power cables damped AC (DAC) voltages monitored by partial discharges and dissipation factor are in use, see below relevant international revived publications and scientific (by international universities) researches regarding the use and world-wide experiences of DAC testing for MV, HV and EHV power cables, see References [1-66].

As a result, different international manufacturers provide a variety of technological solutions.

Save and successful application of DAC technology requests that all relevant testing parameters as requested by the IEC 60060-3, IEEE 400, IEC 60060-3, IEC 60480, IEC 62067, IEC 63026, IEC 60270 and IEEE 400.4 are fulfilled.

Onsite HV is the inventor (1999) of DAC technology as described in the above-mentioned documents and Onsite HV technology fulfils all testing parameters as requested by the IEC 60060-3, IEEE 400, IEEE 400.4, IEC 60060-3, IEC 60480, IEC 62067, IEC 60270, IEC 63026 and IEEE 400.3.

Hardware:

  1. To reduce the energizing time below 100 Sec. a modular power supply with maximum current extendable up to tens of milliampere is available
  2. Modular, synchronized partial discharge (PD) detection extendable with PD detectors at both cable ends (applicable for sensitive PD detection/localization in case of very long cable lengths e.g. above 15 km or longer)
  3. Inductive and resistive system parameters are designed in that way that the system damping factor for the DAC voltage is not more than 15%
  4. All components rugged for on- and offshore onsite conditions e.g. sealed / moisture-controlled system components housing, rugged industrial control computer

User Interface:

  1. Optic data controlling and communication (for optimal EMC conditions)
  2. IEC 60270 conform fully automatic PD calibration e.g. by a wireless device
  3. Full continue display of damped AC test voltage wave and PD signals
  4. Integrated fully automatic system damping factor measurement according to IEC 60060-3
  5. Integrated fully automatic (1 x 10-3 – 10 x 10-2) dissipation factor measurement according to IEEE 400.4

International Regulation:

  1. Referring to IEC 60840, IEC 62067, IEC 63026, IEEE 400.4 test voltage levels requirements for both after laying and maintenance testing
  2. Fulfilling all IEEE 400 and IEEE 400.4 requirements regarding long length cable energizing
  3. Fulfilling all IEC 60270, IEEE 400.3 and IEC 60885-3 requirements regarding PD detection
  4. Fulfilling all IEEE 400.4 and IEC 60060-3 requirements regarding generation of damped AC voltages and dissipation factor measurement

References

  • IEEE 400.4-2015: Guide for Field-Testing of Shielded Power Cable Systems Rated 5 kV and Above with Damped Alternating Current Voltage (DAC)
  • Kreuger, F.H., Industrial High DC Voltage. Delft University Press, 1995, pp. 1–34
  • Dissado, L.A., C. Laurent, G.C. Montanari and. P.H.F. Morshuis, “Demonstrating a Threshold for Trapped Space Charge Accumulation in Solid Dielectrics under dc Fields,” IEEE Transactions on Dielectric and Electrical Insulation, vol. 12, no. 3, 2005, pp 612–620
  • IEEE Std 400.2™, IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (less than 1Hz)
  • Takada T., “Acoustic and Optical Methods for Measuring Electric Charge Distributions in Dielectrics,” IEEE Transactions on Dielectric and Electrical. Insulation, vol.6, no. 5, 1999, pp.519–547
  • Wang, D. Jiang, W. Dong, Z. Ning, J. Xiong and G. Du, „The Effect of Charge Rate on Space Charge Accumulation in Damped Alternating Current (DAC) Testing for Power Cable,” 2018 IEEE International Conference on High Voltage Engineering and Application (ICHVE), 2018, pp. 1-4, doi: 10.1109/ICHVE.2018.8642249
  • Bodega, R., Space charge accumulation in polymeric high voltage DC cable systems, ISBN 90-8559-228-3
  • IEEE 400-2012: Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above
  • IEEE 400.3-2006: Guide for PD Testing of Shielded Power Cable Systems in a Field Environment
  • IEC 60840: Power cables with extruded insulation and the accessories for rated voltages above 30kV up to 150kV test methods and requirements
  • IEC 62067: Power cables with extruded insulation and the accessories for rated voltages above 150kV
  • IEC 63026: Submarine power cables with extruded insulation and their accessories for rated voltages from 6 kV (Um = 7,2 kV) up to 60 kV (Um = 72,5 kV) – Test methods and requirements, 2019
  • HD 632 S2 (CENELEC): Power cables with extruded insulation and their accessories for rated voltages above 36kV (Um=42kV) up to 150kV (Um= 170kV)
  • UK Power Networks, ECP 11-0006, Engineering Commissioning Procedure, ECP 11-0006, HV insulation testing 2018
  • IEC 60270: Partial discharges measurements
  • IEC 60885-3: Test methods for partial discharges measurements on lengths of extruded power cable
  • IEC 60060-3: High Voltage test techniques Part 3: Definitions and requirements for on-site testing
  • Smit, M. van Riet, B. Staarink, Non-destructive after laying test with PD localization, Jicable 2019, paper D3-4
  • Cigre TB 420: Generic Guidelines for Life Time Condition Assessment of HV Assets and Related Knowledge Rules, 2010
  • Cigre TB 627 Condition Assessment for Fluid-Filled Insulation in AC Cables, 2015
  • INMR, Reviewing failure statistics from testing cables & surge arresters, https://www.inmr.com/reviewing-failure-statistics-testing-cables-surge-arresters, 2020
  • Gulski, R. Jongen, B. Quak, J. Parciak, A. Rakowska, Fifteen Years Damped AC Testing and Diagnosis of Transmission power cables, Jicable 2019, paper D3-1
  • Gulski, E. Jongen, R. Rakowska, A. Siodla, K. Offshore Wind Farms On-Site Submarine Cable Testing and Diagnosis with Damped AC. Energies 2019, 12, 3703 https://www.mdpi.com/1996-1073/12/19/3703
  • Cichecki, Testing and Diagnosis of High Voltage and Extra High Voltage Power Cables with Damped AC Voltages ISBN: 978-83-952726-0-8
  • Cigre TB 722: Recommendations for Additional Testing for Submarine Cables from 6kV (Um=7.2 kV) up to 60 kV (Um = 72.5 kV), April 2018
  • J. Wester, E. Gulski and J. J. Smit, „Detection of Partial Discharges at Different AC Voltage Stresses in Power Cables,” in IEEE Electrical Insulation Magazine, vol. 23, no. 4, pp. 28-43, July-Aug. 2007
  • Oyegoke, P. Hyvonen, M. Aro and N. Gao, „Selectivity of damped AC (DAC) and VLF voltages in after-laying tests of extruded MV cable systems,” in IEEE Transactions on Dielectrics and Electrical Insulation, vol. 10, no. 5, pp. 874-882, Oct. 2003
  • Gulski, et al. 2010, Practical aspects of on-site testing diagnosis of transmission power cables in China, International Conference on Condition Monitoring and Diagnosis 2010, Tokyo, Japan, pp. 675-678
  • Bodega, et al., „PD recurrence in cavities at different energizing methods,” in IEEE Transactions on Instrumentation and Measurement, vol. 53, no. 2, pp. 251-258, April 2004
  • Gulski, et al., „Conventional and unconventional partial discharges detection in power cables using different AC voltages,” 2009 IEEE Electrical Insulation Conference, Montreal, QC, 2009, pp. 5-9
  • Cigre TB 662 Guidelines for partial discharge detection using conventional (IEC 60270) and unconventional methods, 2016
  • Cigre TB 841 After laying tests on AC and DC cable systems with new technologies, 2021
  • Cigre TB 852 Recommendations for testing DC extruded cable systems for power transmission at a rated voltage up to and including 800 kV
  • Wester, E. Gulski, J.J. Smit, “Electrical and acoustical PD on-site diagnostics of service aged medium voltage power cables”, 5th International Conference on Power Insulated Cables, Jicable 1999
  • J. Wester, Condition assessment of power cables using partial discharge diagnosis at damped AC voltages, ISBN 90-8559-019-1
  • Cigre TB 680 Implementation of long AC HV and EHV cable systems, 2017
  • P. Seitz, B. Quak, E. Gulski, M. Wild, F. de Vries, Long lengths transmission power cables on-site testing up to 500 kV by damped AC voltages, Jicable 2015
  • Wild S. Tenbolen E. Gulski R. Jongen, Basic aspects of PD on-site testing of long length transmission power cables, IEEE Transactions on Dielectrics and Electrical Insulation, 2017, Volume: 24, Issue: 2, Pages: 1077 – 1087
  • Zhang, T. Huang, Recognition and Location of PD in XLPE Cable under Damped AC Voltage, Cigre 2020, paper B1-213
  • Cigre Technical brochure 226, Knowledge rules for PD diagnosis in service, 2003
  • Cigre Technical brochure 297, Practical aspects of the detection and location of PD in power cables, 2006
  • Cigre Technical brochure 502, High-Voltage On-Site Testing with Partial Discharge Measurement, 2012
  • Niasar, M.G. Wang, X. Kiiza, R.C. Review of PD Activity Considering Very-Low Frequency and Damped Applied Voltage. Energies 2021, 14, 440
  • Jongen R, Gulski, E, Rakowska A, Siodla K, Gall H, After Installation Testing of Inter-array Cables at Offshore Wind Farms using Damped AC Voltages, paper 2019-B10-1, International Conference on Insulated Power Cables, Jicable 2019, Versailles, June 2019
  • Cejka G, Gulski E, Jongen R, Quak B, Parciak J, Rakowska A, Integrated Testing and Diagnosis of Distribution Cables using Damped AC and Very Low Frequency Voltages, Paper 2019-E7-14, International Conference on Insulated Power Cables, Jicable 2019, Versailles, June 2019
  • Leufkens P, Gulski E, Jongen R, Damped AC for Commissioning & Diagnostic Testing of HV Cable Circuits, Proceedings of INMR World Congress (INMR 2019), 20-23 October 2019, Tucson, Arizona, USA, ISBN: 9781713803256
  • Gulski E, Jongen R, Parciak J, Sieminski J, Modern Methods for Quality- and Condition Assessment of High Voltage Cables, VDE High Voltage Technology ETG-Symposium, 2020
  • Gulski, R. Jongen, Condition Based Maintenance of Transmission Power Cables, IEEE Transactions on Power Delivery, TPWRD.2021.3092757 https://ieeexplore.ieee.org/document/9466426
  • Gulski, G. Anders, J. Parciak, J. Sieminski, E. Piesowicz, S. Paszkiewicz, Discussion of Electrical and Thermal Aspects of Offshore Wind Farms Power Cables Reliability, Renewable and Sustainable Energy Reviews, 151 (2021) 111580 https://www.sciencedirect.com/science/article/pii/S1364032121008571
  • PTPiREE, Frame instructions for exploitation of power cables up to 110 kV, 2011
  • PSE, Power cable lines 220 kV and 400 kV, 2020
  • Manuel Wild, Zweiseitige Teilentladungsmessung zur Zustandsbewertung langer Energiekabel, ISBN 978-3-96548-009-4
  • Ronald Plath, „Oscillating voltages“ als Prüfspannung zur Vor-Ort-Prüfung und TE-Messung kunststoffisolierter Kabel, ISBN 3-89574-023-3
  • Gulski, R. Jongen, J. Parciak, Development in Test Methods & Acceptance Criteria for On- & Offshore Power Cables, Proceedings of INMR World Congress (INMR 2022), 16-19 October 2022, Berlin, Germany. https://www.inmr.com/damped-ac-for-commissioning-diagnostic-testing-hv-cable-circuits/
  • P. Leufkens, Cable Testing: State-of-the-Art, Standards & Technological Developments, Proceedings of INMR World Congress (INMR 2022), 16-19 October 2022, Berlin, Germany.
  • Corjanus, M. van Riet, S Staarink, Testing High Voltage Cable Without Ageing the cable Itself, Proceedings of INMR World Congress (INMR 2022), 16-19 October 2022, Berlin, Germany.
  • Gulski, G. J. Anders, R. Jongen, J. Parciak, Damped AC Testing and Diagnosis of Wind Farms HVAC Long Length Cable Circuits, Energies 2022, 15, 8426. / https://doi.org/10.3390/en15228426.
  • Standard Association of Polish Electrical Engineers SEP N SEP-E 004:2022-08, Power and signalling cable lines. Design and construction.
  • Gulski et al. Testing and PD Diagnosis of Transmission Power Cables Using continuous and damped AC Voltages, paper P1-8, Jicable 2023.
  • Jongen et al. Dedicated Cable Testing and Diagnosis Solution to Support a Reliable Renewable Energy Generation, paper P1-3, Jicable 2023.
  • C. LEE, R. WHEATLAND, Field experience on PD measurement for MV cables using different voltage sources, DAC and sinusoidal VLF, CSE N°31 December 2023/ https://cse.cigre.org/cse-n031/field-experience-on-pd-measurement-for-mv-cables-using-different-voltage-sources-dac-and-sinusoidal-vlf.htm
  • Gulski, G.J. Anders, R. Jongen, J. Parciak, H. Putter, D. Götz, Testing and Diagnosis of Power Cables using Damped AC Voltages, Cigre Science and Engineering, CSE no. 29, June 2023. 390/en15228426. https://cse.cigre.org/cse-n029/testing-and-diagnosis-of-power-cables-using-damped-ac-voltages.html
  • P. Leufkens, Cable Testing & Diagnosis: State-of-the-Art, Standards & Technological Developments, Congress (INMR 2023), 12-15 November 2023, Bangkok, Thailand
  • Gulski et al. Testing & Diagnosis of Long-Length Power Cables of On- & Offshore Wind Farms, Congress (INMR 2023), 12-15 November 2023, Bangkok, Thailand
  • ACP OCRP-2024, Recommended Practice for Design, Deployment, and Operation of Submarine Cables in the United States (OCRP5), by American Clean Power Association Standards Committee, 2024
  • Godhwani, B. Cursey, S. Faehang, Enhancing Wind Farm Reliability Through Offline PD Testing with Damped AC Technique, https://ieeexplore.ieee.org/document/10579293
  • E. Gulski, G.J. Anders, J. Parciak, L. Pots, R. Parciak, Technical Benchmarking of Site Acceptance Testing Methods of Offshore Wind Farm HVAC Power Cables, Energies 2025, 18, 6624, https://www.mdpi.com/1996-1073/18/24/6624
Wyjście
Przeiń na górę